| Plan Review Notes For Permit 02110771 |
| Permit Number |
02110771 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-10 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES TO | | | PLANS,AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E. | | | | | | 4} PLEASE NOTE KITCHEN COUNTER- | | | SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 6} PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2',6',12' RULE PER 210-52. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|