Plan Review Notes
Plan Review Notes For Permit 02110762
Permit Number 02110762
Review Stop M
Sequence Number 2
Notes
Date Text
2003-02-03 00:00:00DENIED:
 OUTSIDE AIR SHALL NOT BE TAKEN FROM THE
 ROOF TOP FOR A ONE OR TO FAMILY DWELLING
 AS PER 2001 FBC CHAPTER 13 SECTION
 609.1.ABC.1 #2.PLEASE REVISE
  
 PROVISO:
 MAXIMUM DEVELOPED LENGTH SHALL NOT
 EXCEED 25 FT FROM TE DRYER LOCATION TO
 THE OUTLET TERMINAL-(5 FT REDUCTION FOR
 EACH 90 DEGREE BEND & 2 1/2 FT REDUCTION
 FOR EACH 45 DEGREE BEND) 2001 FBC(M)
 504.6.