Plan Review Notes
Plan Review Notes For Permit 02110762
Permit Number 02110762
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM, A
 VENT IS REQUIRED AT ISLAND SINK IN KIT-
 CHEN. (AAV IS ACCEPTABLE)
 2) SHT P-1 SANITARY RISER DIAGRAM, IS
 AN AIR ADMITTANCE VALVE BEING USED FOR
 THE VENT AT LAUNDRY TUB? IF SO PLEASE
 INDICATE ON PLANS.
 3) SHT P-2 MASTER BATH LAYOUT, MAXIMUM
 DISTANCE OF FIXTURE TRAP FROM VENT EX-
 CEEDS ALLOWABLE DESTANCE FOR SHOWER (6')
 AND TUB (8') PER TABLE 906.1
 4) ALL DEMO'ED PIPING IN SLAB SHALL BE
 INSPECTED PRIOR TO COVERING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377