2002-11-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,LIST SAME ON
 SCHEDULE.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE NOTE PANEL LOCATION
 NEEDS TO MEET 110-26,LOCATION ON PLANS
 IN RELATIONSHIP WITH W/D IS IN VIOLAION.
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 7} PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 8} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
  
 9} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 10} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52E.
  
 11} SHOW LOCATION OF METER & DISCONNECT
 ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392