| 2003-02-12 00:00:00 | PROVISO | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON PLANS,AND RESUBMIT FOR REVIEW. | | | | | | 1} THE FEEDERS FROM THE METER TO THE | | | DISCONNECT ARE NOT RATED FOR 300 AMPS/ | | | 310-15(B)(6). | | | | | | 2} THE RISER DIAGRAM SHOWS 1-3 1/2" | | | CONDIT WITH 2/0'S TO BOTH PANELS,PLEASE | | | CLARIFY. | | | | | | 3} THERE IS A NOTE AT THE BOTTOM OF E-1 | | | THAT INDICATES A 200 AMP SERVICE IS | | | BEING PROVIDED, AND THE EXISTING 100 | | | AMP TO REMAIN,THEN SAY'S TO BE | | | UPGRADED. PLEASE CORRELATE NOTES AND | | | DRAWINGS.THE RISERSHOWS A 300 AMP | | | SERVICE. | | | | | | 4} PLEASE INDICATE THE DISCONNECT | | | LOCATION ON THE STRUCTURE. | | | | | | 5} THE GEC SIZE FOR THE SERVICE MUST BE | | | #2 PER 250-66,THE NOTE ON THE RISER | | | INDICATES #4 OR #2,PLEASE CORRECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|