| Date |
Text |
| 2002-12-03 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES ON |
| | THE PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} CORRECT THE WIRE SIZES ON THE RISER |
| | DIAGRAM.6-350 MCM WONT TERMINATE IN A |
| | 200 AMP PANEL OR METER ENCLOSURE. |
| | |
| | 3} PLEASE SUBMIT LOAD CALCAULATIONS |
| | PER 220,215-5.ALL NEW LOADS PLUS |
| | EXISTING. |
| | |
| | 4} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3.THE "POWDER |
| | ROOM"MUST BE 20A AND #12AWG.ALSO. |
| | |
| | 5} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 6} PLEASE SHOW THE METER AND PANEL |
| | LOCATIONS ON THE PLAN. |
| | |
| | 7} INSTALL A LIGHT,210-70(A),& |
| | RECEPTACLE(210-63)IN THE ATTIC AT THE |
| | LOCATION OF THE AHU. |
| | |
| | 8} THE WHIRPOOL MUST BE GFI PROTECTED |
| | PER 680-70. |
| | |
| | 9} PLEASE CORRELATE OCP WITH |
| | WIRE SIZES.NOTE #10 TO DRYER ON A 2/40. |
| | |
| | 10}SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392 |