| Plan Review Notes For Permit 02110524 |
| Permit Number |
02110524 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-21 00:00:00 | THIS IS A GROUP M OCCUPANCY, SEE FBC | | | 310.1 AND REQUIRES TWO INDEPENDENT | | | EXITS.SEE FBC 1004.2.1 | | | | | | EGRESS IS NOT PERMITTED THROUGH THE | | | KITCHEN AND SIMILAR AREAS, AS SHOWN ON | | | THE PLANS.SEE FBC 1001.1.3.PLEASE | | | REVISE AS NECESSARY. | | | | | | THE PLANS MAKE REFERENCE TO THE SBC, | | | FLORIDA IS CURRENTLY UNDER THE 2001 | | | FLORIDA BUILDING CODE.PLEASE REVISE | | | AS NECESSARY AND ENSURE COMPLIANCE WITH | | | SAME. | | | | | | DO NOT QUOTE THE CODE AS A SUBSTITUTE | | | FOR SPECIFIC DESIGN INFORMATION.SEE | | | FBC 104.2.1. | | | | | | SHOW THE WIND LOAD PRESSURES FOR THE | | | STORE FRONT SYSTEM.SEE FBC 1606.1.7. | | | | | | PLEASE PROVIDE A CLEAR SCOPE OF WORK | | | THAT IS TO BE ACCOMPLISHED WITH THESE | | | PLANS |
|