Plan Review Notes
Plan Review Notes For Permit 02110524
Permit Number 02110524
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-21 00:00:00THIS IS A GROUP M OCCUPANCY, SEE FBC
 310.1 AND REQUIRES TWO INDEPENDENT
 EXITS.SEE FBC 1004.2.1
  
 EGRESS IS NOT PERMITTED THROUGH THE
 KITCHEN AND SIMILAR AREAS, AS SHOWN ON
 THE PLANS.SEE FBC 1001.1.3.PLEASE
 REVISE AS NECESSARY.
  
 THE PLANS MAKE REFERENCE TO THE SBC,
 FLORIDA IS CURRENTLY UNDER THE 2001
 FLORIDA BUILDING CODE.PLEASE REVISE
 AS NECESSARY AND ENSURE COMPLIANCE WITH
 SAME.
  
 DO NOT QUOTE THE CODE AS A SUBSTITUTE
 FOR SPECIFIC DESIGN INFORMATION.SEE
 FBC 104.2.1.
  
 SHOW THE WIND LOAD PRESSURES FOR THE
 STORE FRONT SYSTEM.SEE FBC 1606.1.7.
  
 PLEASE PROVIDE A CLEAR SCOPE OF WORK
 THAT IS TO BE ACCOMPLISHED WITH THESE
 PLANS