| Plan Review Notes For Permit 02110511 |
| Permit Number |
02110511 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-01-06 00:00:00 | ************** NOTES REDLINED ********* | | | | | | 1)NOTE: PLEASE VERFIY AHU KW LOAD. | | | PANEL SCHEDULE AND LOAD CALCS DO NOT | | | CORRELATE. PLEASE CORRELATE OCP/KW/AWG. | | | | | | 2)NOTE: PLEASE SEE WALL/PENINSULAR. | | | EITHER MISSING RECEPT FOR WALL SPACE | | | (210-52) OR RECEPT FOR PENINSULAR | | | COUNTERTOP. 210-52-C-3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | BEFORE ROUGH INSPECTION. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 |
|