Plan Review Notes
Plan Review Notes For Permit 02110511
Permit Number 02110511
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-06 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW LOCATION OF PANEL
 ON PLANS.215-5
  
 2)NOTE: PLEASE NOTE, BATH CIRCUITS ARE
 SHOWN AT 15A #14 AWG. PLEASE SEE 210-52D
 210-11-C3. MUST BE 20A #12.
  
 3)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS REQ`D PER 250-50.
  
 4)NOTE: PLEASE NOTE, ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED. 210-8-A-6
  
 5)NOTE: PLEASE NOTE MISSING GFI RECEPT
 FOR PENINSULAR IN KITCHEN. 210-52-C-3
  
 6)NOTE: PLEASE NOTE, SD IN HALL TO BE
 A MIN OF 3' FROM BATH. NFPA-72 8-1.4.1.6
  
 7)NOTE: PLEASE NOTE, MECH PLANS SHOW
 EXHAUST FANS IN EACH OF THE TWO BATHS,
 BUT NOT SHOWN ON ELECTRICAL PLANS.
  
 8)NOTE: PLEASE NOTE, DISC FOR AHU TO BE
 SHOWN PER 440-11.215-5
  
 PLEASE VERIFY HEATSTRIP FOR HOUSE. SHOWN
 AS 5KW AND MAY BE TOO SMALL FOR A HOUSE
 THIS SIZE.
  
 JUST A NOTE,, PLEASE NOTE IF THERE IS
 GOING TO BE ANY LOW VOLTAGE, CATV OR
 TELEPHONES, PLEASE SHOW LOCATION AT THIS
 TIME IN ORDER TO BE INCLUDED ON THIS
 PERMIT. IF NONE SHOWN, A SEPARATE PERMIT
 APPLICATION/FEES/LAYOUT WILL BE REQ`D AT
 A LATER DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372