| Date |
Text |
| 2002-12-06 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF PANEL |
| | ON PLANS.215-5 |
| | |
| | 2)NOTE: PLEASE NOTE, BATH CIRCUITS ARE |
| | SHOWN AT 15A #14 AWG. PLEASE SEE 210-52D |
| | 210-11-C3. MUST BE 20A #12. |
| | |
| | 3)NOTE: PLEASE INCLUDE FOOTER STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM |
| | AS REQ`D PER 250-50. |
| | |
| | 4)NOTE: PLEASE NOTE, ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS |
| | GFI/GFI PROTECTED. 210-8-A-6 |
| | |
| | 5)NOTE: PLEASE NOTE MISSING GFI RECEPT |
| | FOR PENINSULAR IN KITCHEN. 210-52-C-3 |
| | |
| | 6)NOTE: PLEASE NOTE, SD IN HALL TO BE |
| | A MIN OF 3' FROM BATH. NFPA-72 8-1.4.1.6 |
| | |
| | 7)NOTE: PLEASE NOTE, MECH PLANS SHOW |
| | EXHAUST FANS IN EACH OF THE TWO BATHS, |
| | BUT NOT SHOWN ON ELECTRICAL PLANS. |
| | |
| | 8)NOTE: PLEASE NOTE, DISC FOR AHU TO BE |
| | SHOWN PER 440-11.215-5 |
| | |
| | PLEASE VERIFY HEATSTRIP FOR HOUSE. SHOWN |
| | AS 5KW AND MAY BE TOO SMALL FOR A HOUSE |
| | THIS SIZE. |
| | |
| | JUST A NOTE,, PLEASE NOTE IF THERE IS |
| | GOING TO BE ANY LOW VOLTAGE, CATV OR |
| | TELEPHONES, PLEASE SHOW LOCATION AT THIS |
| | TIME IN ORDER TO BE INCLUDED ON THIS |
| | PERMIT. IF NONE SHOWN, A SEPARATE PERMIT |
| | APPLICATION/FEES/LAYOUT WILL BE REQ`D AT |
| | A LATER DATE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |