| 2002-11-15 00:00:00 | PROVISO: | | | | | | PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE 3M FIREWRAP ON THE | | | JOBSITE AT THE OF INSPECTION. | | | | | | DUCTWORK SHALL NOT BE COVERED PRIOR TO | | | INSPECTION OF WELDS. | | | | | | CLARIFY NOTE ON PLAN SHEET 2 OF 2 | | | BUILDING SECTION DETAIL #1, "ACCESS | | | DOOR TO FIRE DAMPER IN MUA COLLAR". | | | WILL A FIRE DAMPER BE INSTALLED IN THE | | | MAKE-UP AIR DUCT? | | | | | | AS PER 2001 FBC(M) 506.3.14.3, EXHAUST | | | OUTLETS SHALL BE LOCATED NOT LESS THAN | | | 10 FT FROM PARTS OF THE SAME OR | | | CONTIGUOUS BUILDING OR ADJACENT PROPERTY | | | LINE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|