| Plan Review Notes For Permit 02110368 |
| Permit Number |
02110368 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | REVISION CHECKLIST: | | | 1-ARCHITECT NEEDS TO REVIEW ENGINEERING | | | CALCULATIONS AND SPECS AND REVISE THE | | | DIAPHRAGM SCHEDULE AS REQUIRED. | | | 2-SHEET A-3: RIGHT ELEVATION TO MATCH | | | BUILDING SECTION A-3. TOP OF BB WAS | | | RAISED. NOTE #4 DOESN'T APPLY AT WALL | | | AREA ON ZERO LOT LINE. *REVISE HEIGHT | | | OF BB ON ALL ELEVATIONS AS WELL. ALSO, | | | REVISE HT. OF BB ON ROOF FRAMING PLAN. | | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT AS | | | REQUESTED ON PROVISO DATED 12-5-02. | | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | | 41/S1. NEED ANCHOR COMPLETE SIZE AND | | | WASHER. SEC. 104.2.1.2 CITY AMENDMENTS | | | 5-SHEET S-2: DETAIL 8/S2 WAS INCORRECTLY | | | KEYED. SEE PLANS. |
|