| Plan Review Notes For Permit 02110368 |
| Permit Number |
02110368 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR | | | FIRE RATED WALL ASSEMBLY AT ZERO LOT | | | LINE WALL. TABLE REFERENCED ON DETAIL | | | 11/S3 IS FOR CONCRETE ASSEMBLIES, NOT | | | FOR WOOD. SEE SECTION 709.6 FBC FOR | | | WOOD ASSEMBLIES AND REVISE DETAIL AS | | | REQUIRED. ALSO, COMPLETE DETAIL | | | INCLUDING ASEMBLY REQUIRED AT EXTERIOR | | | SIDE. NEED ONE HR FROM INTERIOR AND | | | EXTERIOR EXPOSURE TO FIRE AS REQUIRED | | | BY TABLE 600 FBC 2001. | | | 2-ARCHITECT TO REVISE THE DIAPHRAGM | | | SCHEDULE TO MATCH ENGINEERING ANALYSIS | | | AND SPECIFICATIONS. | | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | | 41/S1. NEED ANCHOR SIZE AND WASHER. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
|