| 2002-12-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-REVISE SECTION 3 ON SHEET S2 TO MATCH | | | THE DIAPHRAGM SCHEDULE REGARDING SIZE | | | OF NAILS. | | | 2-GLASS BLOCK TO BE SAFETY GLASS IF FACE | | | THICKNESS IS LESS THAN 0.25" AS REQ'D | | | BY SEC. 2405.2.2 FBC 2001. | | | 3-PROVIDE SOIL TEST REPORT. | | | 4-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. |
|