| Plan Review Notes For Permit 02110363 |
| Permit Number |
02110363 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | REVISION CHECKLIST: | | | 1-ARCHITECT NEEDS TO REVIEW ENGINEERING | | | CALCULATIONS AND SPECS AND REVISE THE | | | DIAPHRAGM SCHEDULE AS REQUIRED. | | | 2-SHEET A-3: REVISE RIGHT ELEVATION TO | | | MATCH BUILDING SECTION A/A-3. TOP OF | | | BB WAS RAISED TO AVOID 1HR. FIRE RATED | | | ASSEMBLY AT TRUSS HEEL @ ZERO LOT LINE | | | WALL. SEE PLANS FOR COMMENTS. | | | ALSO, REVISE BEAM HEIGHT SHOW ON OTHER | | | ELEVATIONS AND ROOF FRAMING PLAN. | | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT AS | | | REQUESTED ON PROVISO DATED 12-15-02. | | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | | 41/S1. NEED COMPLETE SIZE OF ANCHOR & | | | WASHER. SEC. 104.2.1.2 CITY AMENDMENTS | | | 5-SHEET S-2: DETAIL 8/S-2 WAS KEYED | | | INCORRECTLY. SEE PLAN AND REVISE AS | | | REQUIRED. |
|