2002-11-07 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT SHOW
 WHAT SIZE OCP IS FEEDING BOTH "PEG AND
 GP"? PLEASE SHOW.
  
 2)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3/230-42
 ETC.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GFI RECEPT FOR RTU. 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372