| 2002-11-07 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE, PLANS DO NOT SHOW | | | WHAT SIZE OCP IS FEEDING BOTH "PEG AND | | | GP"? PLEASE SHOW. | | | | | | 2)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. 215-3/230-42 | | | ETC. | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | GFI RECEPT FOR RTU. 210-63 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|