| Plan Review Notes For Permit 02110313 |
| Permit Number |
02110313 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-04-07 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE PLANS. PLANS WERE | | | SUBMITTED AS A RE-STAMP AND THEY HAVE | | | BEEN REVISED. SERVICE IS NOW SHOWN AS | | | 200A? | | | PLEASE ALSO SEE THAT THERE IS NO AIC | | | RATINGS SHOWN ANYMORE AS SHOWN ON LAST | | | SET.?? | | | PLEASE ALSO SEE, EQUIPMENT GROUNDING | | | CONDUCTOR IS STILL MISSING BETWEEN MAIN | | | DISC AND PANEL. | | | | | | | | | 2)NOTE: PLEASE SUBMIT TWO SETS OF PLANS | | | FOR REVIEW. PLEASE PAY FEES FOR REVISION | | | -S. PLEASE SHOW REVISIONS BY CLOUDS AND/ | | | /OR TRIANGLES AND DATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|