| Plan Review Notes For Permit 02110313 |
| Permit Number |
02110313 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-01-24 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT, IT IS NOTED | | | FOR PANELS MAIN AND SUB-PANEL, BUT NOT | | | FOR MAIN DISCONNECT. 110-9 | | | | | | 2)NOTE: PLEASE MISSING EQUIPMENT GROUND- | | | ING CONDUCTORS BETWEEN MAIN DISC AND | | | PANEL "A" AND TO SUB PANEL. SIZE PER | | | 250-122. | | | | | | 3)NOTE: PLEASE SHOW HOW SUB PANEL IS | | | BEING FED. PLEASE SEE MAIN PANEL,PLEASE | | | NOTE NOTHING SHOWN FOR FEED TO SUB PANEL | | | | | | | | | 4)NOTE: PLEASE SEE CONNECTED LOAD ON | | | WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR | | | PLEASE NOTE LOAD NOT TO EXCEED 80% OF | | | BRKR RATING.PLEASE ADJUST. | | | | | | 5)NOTE: PLEASE SEE 240-6 FOR STANDARD | | | OCP FOR AHU'S. | | | | | | 6)NOTE: PLEASE CLARIFY RISER SHOWING | | | ONE A/C UNIT FROM MAIN PANEL AND ONE | | | FROM SUB PANEL, PLEASE SEE PANEL SCHED-- | | | ULE AND NOTE BOTH ARE SHOWN FROM SUB- | | | -PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|