2003-01-24 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT, IT IS NOTED
 FOR PANELS MAIN AND SUB-PANEL, BUT NOT
 FOR MAIN DISCONNECT. 110-9
  
 2)NOTE: PLEASE MISSING EQUIPMENT GROUND-
 ING CONDUCTORS BETWEEN MAIN DISC AND
 PANEL "A" AND TO SUB PANEL. SIZE PER
 250-122.
  
 3)NOTE: PLEASE SHOW HOW SUB PANEL IS
 BEING FED. PLEASE SEE MAIN PANEL,PLEASE
 NOTE NOTHING SHOWN FOR FEED TO SUB PANEL
  
  
 4)NOTE: PLEASE SEE CONNECTED LOAD ON
 WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR
 PLEASE NOTE LOAD NOT TO EXCEED 80% OF
 BRKR RATING.PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240-6 FOR STANDARD
 OCP FOR AHU'S.
  
 6)NOTE: PLEASE CLARIFY RISER SHOWING
 ONE A/C UNIT FROM MAIN PANEL AND ONE
 FROM SUB PANEL, PLEASE SEE PANEL SCHED--
 ULE AND NOTE BOTH ARE SHOWN FROM SUB-
 -PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372