Plan Review Notes For Permit 02110313
Permit Number 02110313
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-23 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED. MUST
 MEET 2001 FBC PLUMBING REQUIREMENTS. SEE
 SEC. 909.1 WET VENTS.
 1.THE WET VENT FOR THE BATHROOM GROUP
 MUST BE AT THE UPSTREAM SIDE OF THE
 FIXTURE IT SERVES.
 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO
 THE WET VENT FOR A BATHROOM GROUP.
  
 PLUMBING PLAN REVIEW BY;