2002-11-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLLED. PLEASE
 NOTE, MAINS/PANELS/BRKRS ARE TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 110-9/215-5
  
 2)NOTE: PLEASE NOTE; THERE ARE MANY
 ITEMS ON LOAD CALCULATIONS THAT DO
 NOT CORRELATE WITH PANEL SCHEDULE.
 ALSO,ITEMS ON PANEL SCHEDULE THAT ARE
 NO IN LOAD CALCS.
  
 3)NOTE: PLEASE SEE 424-3C FOR MIN 125%
 FOR OCP OF AHU`S. PLEASE SEE LOAD CALCS,
 AHU`S SHOWN AT 10KW EACH. MIN OCP SHOULD
 NOT BE 45A AND #8.
  
 4)NOTE: PLEASE CLARIFY, LOAD CALCS SHOW
 TWO GRARGE DOOR OPENERS AND PLANS ONLY
 SHOW ONE?
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO COLD WATER AND
 FOOTER STEEL. PER 250-50
  
 6)NOTE: PLEASE SHOW CONDUCTOR SIZE
 BETWEEN METER AND MAIN.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVOEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  