Plan Review Notes
Plan Review Notes For Permit 02110308
Permit Number 02110308
Review Stop E
Sequence Number 2
Notes
Date Text
2003-01-24 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW SERVICE EQUIPMENT.IT IS NOTED
 SHOWN FOR PANELS, BUT NOT FOR MAIN DISC.
 110-9
  
 2)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN DISC AND PANEL
 "A", ALSO MISSING BETWEEN "A" AND SUB-
 -PANEL? SIZE PER 250-122.
  
 3)NOTE: PLEASE SHOW HOW SUB PANEL IS
 BEING FED? PLEASE SEE PANEL SCHEDULE FOR
 "A", NOTHIN SHOWN FOR SUB PANEL. PLEASE
 SHOW OCP, AND LOAD.
  
 4)NOTE: PLEASE SEE CONNECTED LOAD ON
 WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR,
 PLEASE NOTE, LOAD NOT TO EXCEED 80% OF
 BRKR. PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240-6 FOR RATINGS
 OF OCP FOR AHU'S. SHOWN AS 65A BRKR.
  
 6)NOTE: PLEASE CLARIFY, RISER DIAGRAM
 SHOWS ONE A/C UNIT FROM SUB-PANEL AND
 ONE FROM MAIN PANEL, WHERE AS PANEL
 SCHEDULE FOR SUB-PANEL SHOWS BOTH??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIOEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER'
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372