| Plan Review Notes For Permit 02110308 |
| Permit Number |
02110308 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-01-24 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL NEW SERVICE EQUIPMENT.IT IS NOTED | | | SHOWN FOR PANELS, BUT NOT FOR MAIN DISC. | | | 110-9 | | | | | | 2)NOTE: MISSING EQUIPMENT GROUNDING | | | CONDUCTORS BETWEEN MAIN DISC AND PANEL | | | "A", ALSO MISSING BETWEEN "A" AND SUB- | | | -PANEL? SIZE PER 250-122. | | | | | | 3)NOTE: PLEASE SHOW HOW SUB PANEL IS | | | BEING FED? PLEASE SEE PANEL SCHEDULE FOR | | | "A", NOTHIN SHOWN FOR SUB PANEL. PLEASE | | | SHOW OCP, AND LOAD. | | | | | | 4)NOTE: PLEASE SEE CONNECTED LOAD ON | | | WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR, | | | PLEASE NOTE, LOAD NOT TO EXCEED 80% OF | | | BRKR. PLEASE ADJUST. | | | | | | 5)NOTE: PLEASE SEE 240-6 FOR RATINGS | | | OF OCP FOR AHU'S. SHOWN AS 65A BRKR. | | | | | | 6)NOTE: PLEASE CLARIFY, RISER DIAGRAM | | | SHOWS ONE A/C UNIT FROM SUB-PANEL AND | | | ONE FROM MAIN PANEL, WHERE AS PANEL | | | SCHEDULE FOR SUB-PANEL SHOWS BOTH?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIOEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER' | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|