Date Text
2002-11-23 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED. MUST
 MEET 2001 FBC PLUMBING REQUIREMENTS.
 SEE SEC. 909.1 WET VENTS.
 1.THE WET VENT FOR THE BATHROOM GROUP
 MUST BE AT THE UP STREAM SIDE OF THE
 FIXTURES IT SERVES.
 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO
 THE WET VENT FOR A BATHROOM GROUP.
 PLUMBING PLAN REVIEW BY;