| Plan Review Notes For Permit 02110308 |
| Permit Number |
02110308 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-27 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMITAIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS, PANELS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. 110-9 | | | | | | 2)NOTE: PLEASE NOTE, THERE ARE MANY | | | ITEMS ON PANEL SCHEDULE AND LOAD CALCS | | | THAT DO NOT CORRELATE. PLEASE ADJUST. | | | THERE ARE ALSO ITEMS ON LOAD CALCS | | | NOT ON PANEL SCHEDULE? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE 424-3C FOR OCP OF | | | AHU/HEAT. 125% MIN. AHU`S SHOWN AS 10KW | | | W/ #8 AND 2P45A`S. PLEASE ADJUST | | | | | | 4)NOTE: PLEASE CLARIFY LOAD CALCS. | | | LIST TWO GARAGE DOOR OPENERS AND ONLY | | | ONE SHOWN ON PLANS. | | | | | | 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | CONDUCTOR TO FOOTER STEEL ALSO PER | | | 250-50. | | | | | | 6)NOTE: PLEASE SHOW SIZE IF CONDUCTORS | | | BETWEEN MAIN AND METER.215-5/310-15 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|