| 2002-12-18 00:00:00 | ****************UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, SOME NOTES FROM | | | FIRST REVIEW WERE NOT ADDRESSED. | | | | | | 2)NOTE: PLEASE SEE 230-95, PLEASE | | | CLARIFY WHERE PLANS/RISER ARE SHOWING | | | GFI PROTECTION FOR SERVICE. | | | | | | 3)NOTE: PLEASE SEE 240-3C | | | FOR SIZING OF SERVICE ENTRANCE CONDUCTOR | | | -S. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCS, PLANS | | | NOW SHOW LOADS ON PANELS X 125%?? | | | PLEASE CLARIFY WHERE LOAD CALCS ARE | | | SHOWN PER 220,,, | | | ALSO 220-12. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|