| Plan Review Notes For Permit 02110243 |
| Permit Number |
02110243 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-22 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON PROPER | | | BUILDING ELEVATION. | | | | | | 2) NEW FABRIC AWNINGS ARE TO BE FIRE | | | RETARDANT. | | | | | | 3) FIRE SPRINKLER PROTECTION IS REQUIRED | | | UNDER LOADING DOCK CANOPIES WHERE | | | COMBUSTIBLE MATERIALS ARE EXPECTED. | | | | | | 4) EGRESS DOORS SHALL ALLOW FOR FREE | | | EGRESS FROM THE INTERIOR SIDE OF THE | | | STORE. EXITING SHALL NOT REQUIRE "THE | | | USE OF KEY, TOOL, SPECIAL KNOWLEDGE | | | OR EFFORT". | | | | | | 5) SECURITY DEVICES OR LOCKS ON EXIT | | | DOORS SHALL COMPLY WITH SPECIAL | | | LOCKING DEVICES OR ACCESS CONTROLLED | | | LOCKS. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM AND FIRE | | | SPRINKLER SYSTEM. | | | | | | 7) A MAIN AISLE OF AT LEAST 5 FEET | | | WIDE SHALL BE PROVIDED TO EXITS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|