| Notes |
| Date |
Text |
| 2002-11-19 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CLARIFY CIRCUITS TO | | | RECEPTS SHOWN W/ #8 CONDUCTORS? PLEASE | | | NOTE CONDUIT FILL ,SHOWN W/ 4-#8 IN | | | 3/4 "CONDUIT.5-#8`S ALSO IN 3/4" | | | NEC TABLE 9 | | | | | | 2)NOTE: PLEASE NOTE BRANCG CIRCUITS | | | FOR EM LT AND EX LTS TO MEET 700-12E | | | | | | 3)NOTE: PLEASE CLARIFY GFI PROTECTION | | | FOR SERVICE 230-95. | | | | | | 4)NOTE: PLEASE CLARIFY ATTACHMENT FOR | | | TRANSFORMER PER 250-30 | | | | | | | | | | | | | | | | | | | | | | | | 6)NOTE: PLEASE SHOW ALL LOAD CALCULATION | | | -S PER 215-,220-3,220-10,220-11,220-13 | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%. 215-3/233-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|