| Date |
Text |
| 2002-11-13 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02110242 |
| | ADD: 505 S FLAGLER/ 1500 |
| | CONT: ANDERSON MOORE |
| | TEL: (561)627-4744 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) 412.6.1 HISE RISE, ALL ELEVATORS ON |
| | ALL FLOORS SHALL OPEN INTO ELEVATOR LOB- |
| | BIES WHICH ARE SEPERATED FROM THE REMAIN |
| | DER OF THE BUILDING BY ONE HOUR FIRE |
| | RESISTANT CONSTRUCTION WITH 20-MINUTE |
| | OPENING PROTECTIVES. |
| | |
| | 2) OPENINGS IN ELEVATOR LOBBY SHALL BE |
| | LIMITED TO THOSE FOR ACCESS TO THE |
| | ELEVATOR AND FOR EGRESSTO THE BUILDING. |
| | ALL ROOMS AND ENCLOSURES SHALL HAVE AT |
| | LEAST ONE REQUIRED EXIT ACCESSIBLE WITH- |
| | OUT TRAVEL THROUGH THE ELEVATOR LOBBY. |
| | EXIT STAIWAYS, CHUTES,JANITORS CLOSETS, |
| | GUEST ROOMS, SERVICE ROOMS, ETC SHALL |
| | NOT OPEN INTO THE ELEVATOR LOBBY. |
| | SEE HVAC ROOM, ELEC ROOM, STAIRS. |
| | |
| | 3) 412.6.3 EACH ELEVATOR LOBBY SHALL BE |
| | PROVIDED WITH APPROVED SMOKE DETECTOR |
| | LOCATED ON THE ELEVATOR CEILING. |
| | |
| | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 5)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 6) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |