Plan Review Notes
Plan Review Notes For Permit 02110242
Permit Number 02110242
Review Stop B
Sequence Number 1
Notes
Date Text
2002-11-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02110242
 ADD: 505 S FLAGLER/ 1500
 CONT: ANDERSON MOORE
 TEL: (561)627-4744
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 412.6.1 HISE RISE, ALL ELEVATORS ON
 ALL FLOORS SHALL OPEN INTO ELEVATOR LOB-
 BIES WHICH ARE SEPERATED FROM THE REMAIN
 DER OF THE BUILDING BY ONE HOUR FIRE
 RESISTANT CONSTRUCTION WITH 20-MINUTE
 OPENING PROTECTIVES.
  
 2) OPENINGS IN ELEVATOR LOBBY SHALL BE
 LIMITED TO THOSE FOR ACCESS TO THE
 ELEVATOR AND FOR EGRESSTO THE BUILDING.
 ALL ROOMS AND ENCLOSURES SHALL HAVE AT
 LEAST ONE REQUIRED EXIT ACCESSIBLE WITH-
 OUT TRAVEL THROUGH THE ELEVATOR LOBBY.
 EXIT STAIWAYS, CHUTES,JANITORS CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
 SEE HVAC ROOM, ELEC ROOM, STAIRS.
  
 3) 412.6.3 EACH ELEVATOR LOBBY SHALL BE
 PROVIDED WITH APPROVED SMOKE DETECTOR
 LOCATED ON THE ELEVATOR CEILING.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved