Plan Review Notes
Plan Review Notes For Permit 02110223
Permit Number 02110223
Review Stop R
Sequence Number 2
Notes
Date Text
2003-03-10 00:00:00SUBMITTAL CHECKLIST:
 1-ARCHITECT TO REVIEW THE ENGINEERING
 CALCULATIONS AND REVISE THE DIAPHRAGM
 SCHEDULE AS REQUIRED.
 2-SHEET A-3: REVISE THE RIGHT ELEVATION
 TO MATCH BUILDING SECTION A/A3.TOP
 OF BB WAS RAISED TO AVOID HAVING ONE
 HR FIRE RATED ASSEMBLY AT TRUSS HEEL
 AS REQUIRED BY TABLE 600 FBC 2001.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT AS
 REQUIRED ON PROVISO DATED 12-10-02.
 4-PROVIDE COMPLETE INFORMATION ON DETAIL
 41/S1. NEED COMPLETE ANCHOR SIZE AND
 WASHER. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 5-SHEET S-2: DETAIL 8/S2 ON 2ND FLOOR
 FRAMING PLAN WAS KEYED INCORRECTLY.
 SEE PLAN AND REVISE AS REQUIRED.