| Plan Review Notes For Permit 02110223 |
| Permit Number |
02110223 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-10 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-ARCHITECT TO REVISE DETAIL FOR ONE HR | | | WALL ASSEMBLY AT ZERO LOT LINE. | | | TABLE REFERENCED ON DETAIL 11/S3 IS | | | FOR CONCRETE WALL ASSEMBLIES, NO WOOD. | | | SEE SECTION 709.6 FOR WOOD ASSEMBLIES | | | AND PROVIDE COMPLETE DETAIL FOR ONE HR | | | ASSEMBLY WITH PROTECTION FROM BOTH | | | SIDES, INTERIOR AND EXTERIOR AS REQ'D | | | BY TABLE 600 FBC 2001. | | | 2-ARCHITECT TO REVISE THE DIAPHRAGM | | | SCHEDULE TO MATCH ENGINEERING ANALYSIS | | | AND SPECIFICATIONS. | | | 3-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 4-PROVIDE COMPLETE INFORMATION ON DETAIL | | | 41/S1. NEED ANCHOR SIZE AND WASHER TO | | | BE USED. SEC. 104.2.1.2 CITY AMENDMENT |
|