| 2004-09-21 00:00:00 | ****CORRECTIONS**** | | | FAX DATED 8/30/2004 PREPARED BY SLA | | | ARCHITECTS AND PLANNERS INC. | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | THIS LETTER SERVES AS A CURSORY REVIEW | | | OF THE SKETCH AND LETTER SUBMITTED | | | REGARDING THE USE OF A PLATFORM LIFT | | | RATHER THAN AN ELEVATOR.ONLY FBC2001 | | | COMPLIANCE WAS TAKEN INTO CONSIDERATION; | | | FOR A MORE COMPLETE REVIEW INCLUDING | | | OTHER TRADES, INCLUDING FIRE, PLEASE | | | SUBMIT AS A REVISION. | | | | | | VERTICAL ACCESSIBILITY IS REQUIRED FBC | | | 11-4.1.3.THE EXCEPTIONS IN 11-4.1.3(5) | | | DO NOT APPEAR TO APPLY TO THIS JOB. | | | RELIEF FROM THIS REQUIREMENT MAY BE | | | REQUESTED FROM THE BUILDING OFFICIAL | | | IN WRITING; PLEASE ADDRESS TO NEIL K. | | | MELICK. | | | | | | FIRE RESISTANCE OF THE PROPOSED LIFT | | | WOULD BE DETERMINED BY FBC704.2.1.2 AND | | | FBC TABLE 705.1.2.YOUR APPROVED PLAN | | | INDICATES A 1 HR FLOOR/CEILING ASSEMBLY | | | RATING. |
|