2004-06-24 00:00:00PROVISO:
 PLEASE NOTE HVAC PLANS SUBMITTED ARE RED
 LINED BY THE A/C CONTRACTOR.FUTURE
 SUBMITTALS OR REVISIONS, PLEASE REFLECT
 THE DELETION OF DUCT PENETRATION THROUGH
 THE STAIRWELL.
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS ON
 THE JOBSITE AT TIME OF INSPECTION.
  
 PLAN INDICATES AHU 1 & 2 - MAXIMUM CFM
 WILL BE 1,800.PROVIDE DOCUMENTATION OF
 MANUFACTURERS ENGINEERING DATA VERIFYING
 THE UNITS CAN NOT EXCEED 2,000 CFM,
 OTHERWISE DUCT SMOKE DETECTORS WILL BE
 REQUIRED.
  