| Plan Review Notes For Permit 02110220 |
| Permit Number |
02110220 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-06-24 00:00:00 | PROVISO: | | | PLEASE NOTE HVAC PLANS SUBMITTED ARE RED | | | LINED BY THE A/C CONTRACTOR.FUTURE | | | SUBMITTALS OR REVISIONS, PLEASE REFLECT | | | THE DELETION OF DUCT PENETRATION THROUGH | | | THE STAIRWELL. | | | | | | PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPERS ON | | | THE JOBSITE AT TIME OF INSPECTION. | | | | | | PLAN INDICATES AHU 1 & 2 - MAXIMUM CFM | | | WILL BE 1,800.PROVIDE DOCUMENTATION OF | | | MANUFACTURERS ENGINEERING DATA VERIFYING | | | THE UNITS CAN NOT EXCEED 2,000 CFM, | | | OTHERWISE DUCT SMOKE DETECTORS WILL BE | | | REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|