| Plan Review Notes For Permit 02110220 |
| Permit Number |
02110220 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-03-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) FROM PREVIOUS REVIEW: A WATER RISER | | | DIAGRAM IS REQUIRED PER SEC 104.3.1.1. | | | AIR CHAMBERS ARE NOT APPROVED - IF USING | | | WATER HAMMER ARRESTORS, THEY SHALL BE | | | LOCATED NEAR THE FIXTURES, IN AN "EFFECT | | | IVE RANGE" NOT IN THE CEILING PER PDI-WH | | | 201 AND MANUF. INSTALL. INSTRUCTIONS. | | | SECTION 604.9 | | | 2) CERTIFICATE OF AUTHORIZATION REQUIRED | | | ON TITLE BLOCK. FS 481.219 | | | 3) FAC 61G1-16.004 PRINTED NAME OF PER- | | | SON SEALING PLANS REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|