Plan Review Notes
Plan Review Notes For Permit 02110220
Permit Number 02110220
Review Stop P
Sequence Number 3
Notes
Date Text
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: A WATER RISER
 DIAGRAM IS REQUIRED PER SEC 104.3.1.1.
 AIR CHAMBERS ARE NOT APPROVED - IF USING
 WATER HAMMER ARRESTORS, THEY SHALL BE
 LOCATED NEAR THE FIXTURES, IN AN "EFFECT
 IVE RANGE" NOT IN THE CEILING PER PDI-WH
 201 AND MANUF. INSTALL. INSTRUCTIONS.
 SECTION 604.9
 2) CERTIFICATE OF AUTHORIZATION REQUIRED
 ON TITLE BLOCK. FS 481.219
 3) FAC 61G1-16.004 PRINTED NAME OF PER-
 SON SEALING PLANS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]