| Plan Review Notes For Permit 02110220 |
| Permit Number |
02110220 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-03-25 00:00:00 | DENIED: | | | 1.PLANS INDICATE 6" DUCT PENETRATING | | | THROUGH THE STAIRWELL.PER FBC | | | 1006.1.3.1, DUCTWORK SHALL NOT | | | PENETRATE OR RUN THROUGH A STAIRWAY | | | ENCLOSURE UNLESS IT IS A PART OF THE | | | STAIRWAY PRESSURIZATION SYSTEM. | | | | | | 2.PLEASE NOTE THE LOCATION OF THE | | | FRESH AIR INTAKE TO THE FIRST FLOOR | | | AHU. FRESH AIR INTAKES SHALL BE LOCATED | | | AS NOT TO RECIRCULATE HOT AIR EMITTED | | | OF THE CONDENSING UNITS. | | | | | | 3.PROVIDE SUBMITTAL DATA OR LETTER | | | FROM TRANE INDICATING THAT UNDER NO | | | CIRCUMSTANCE CAN THE A/C SYSTEM EXCEED | | | 2,000 CFM, OTHERWISE DUCT SMOKE | | | DETECTORS WILL BE REQUIRED.2001 | | | FBC(M) 606.2.1, DUCT SMOKE DETECTORS | | | SHALL BE INSTALLED IN SYSTEMS WITH THE | | | "DESIGN CAPACITY" GREATER THAN 2,000 | | | CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|