2004-03-25 00:00:00DENIED:
 1.PLANS INDICATE 6" DUCT PENETRATING
 THROUGH THE STAIRWELL.PER FBC
 1006.1.3.1, DUCTWORK SHALL NOT
 PENETRATE OR RUN THROUGH A STAIRWAY
 ENCLOSURE UNLESS IT IS A PART OF THE
 STAIRWAY PRESSURIZATION SYSTEM.
  
 2.PLEASE NOTE THE LOCATION OF THE
 FRESH AIR INTAKE TO THE FIRST FLOOR
 AHU. FRESH AIR INTAKES SHALL BE LOCATED
 AS NOT TO RECIRCULATE HOT AIR EMITTED
 OF THE CONDENSING UNITS.
  
 3.PROVIDE SUBMITTAL DATA OR LETTER
 FROM TRANE INDICATING THAT UNDER NO
 CIRCUMSTANCE CAN THE A/C SYSTEM EXCEED
 2,000 CFM, OTHERWISE DUCT SMOKE
 DETECTORS WILL BE REQUIRED.2001
 FBC(M) 606.2.1, DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN SYSTEMS WITH THE
 "DESIGN CAPACITY" GREATER THAN 2,000
 CFM.
  