2004-04-07 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
 THIRD PLAN REVIEW. PLANS BY SLA
 ARCHITECTS DATED 1/29/04.
  
 DETAILS 2/A1 AND 3/A1 DEPICT BEVELED
 WINDOW BUCKS.SEE FBC 1707.4.4.2
 REGARDING FULL SUPPORT.
  
 SHEET A2.PROVIDE A DETAIL FOR THE
 WINDOWS TO BE CUT IN TO HAVE HEADERS OR
 LINTELS.SEE FBC 104.2 AS AMENDED
  
 SHEET A3, THE 42" HIGH STAIR GUARD RAIL.
 THE BOTTOM RAIL MUST BE 2" OR LESS ABOVE
 THE FLOOR.SEE FBC 1015.3.
  
 SHEET A3 SHOWS A 45 MIN RATED DOOR ON
 THE FIRST FLOOR FOR THE STAIR SHAFT.A
 ONE HOUR RATING IS REQUIRED AND THE
 SHAFT WALL CONTINUOUS.SEE FBC
 704.2.1.2 AND FBC TABLE 705.1.2.
  
 THE A/C PLAN STILL SHOWS A DUCT
 PENETRATING THE EXIT STAIR ENCLOSURE.
 SEE FBC 1006.1.3.1 AND NFPA 101
 7.1.3.2.1 (E).THE REFERENCE TO DUCTS
 IS FOR STAIR PRESSURIZATION NOT AIR
 CONDITIONING.
  
 THE A/C SHEET IS NOT SEALED BY THE
 ARCHITECT.
  
 SHEET A3 CONTAINS A NOTE REFERENCING
 ACCESSIBILITY.THE 11.1.6 (I) (F)
 SECTION CITED IS NOT FOUND IN THE FBC.
 PLEASE SEE FBC 11-4.1.3 (5) AND FBC
 11-4.1.6 (1), VERTICAL ACCESIBILITY IS
 REQUIRED.
  
 THE TRACO WINDOW NOA HAS ILLEGIBLE
 DRAWINGS.
  
 THE PLANS DO NOT SHOW THE PRESSURES FOR
 THE WINDOW DESIGN.SEE FBC 1606.1.7 #5.
  
 SEE PREVIOUS NOTES REGARDING IMPACT
 FEES.