| 2004-04-07 00:00:00 | PLAN REVIEW NOT A PERMIT APPLICATION. |
| | THIRD PLAN REVIEW. PLANS BY SLA |
| | ARCHITECTS DATED 1/29/04. |
| | |
| | DETAILS 2/A1 AND 3/A1 DEPICT BEVELED |
| | WINDOW BUCKS.SEE FBC 1707.4.4.2 |
| | REGARDING FULL SUPPORT. |
| | |
| | SHEET A2.PROVIDE A DETAIL FOR THE |
| | WINDOWS TO BE CUT IN TO HAVE HEADERS OR |
| | LINTELS.SEE FBC 104.2 AS AMENDED |
| | |
| | SHEET A3, THE 42" HIGH STAIR GUARD RAIL. |
| | THE BOTTOM RAIL MUST BE 2" OR LESS ABOVE |
| | THE FLOOR.SEE FBC 1015.3. |
| | |
| | SHEET A3 SHOWS A 45 MIN RATED DOOR ON |
| | THE FIRST FLOOR FOR THE STAIR SHAFT.A |
| | ONE HOUR RATING IS REQUIRED AND THE |
| | SHAFT WALL CONTINUOUS.SEE FBC |
| | 704.2.1.2 AND FBC TABLE 705.1.2. |
| | |
| | THE A/C PLAN STILL SHOWS A DUCT |
| | PENETRATING THE EXIT STAIR ENCLOSURE. |
| | SEE FBC 1006.1.3.1 AND NFPA 101 |
| | 7.1.3.2.1 (E).THE REFERENCE TO DUCTS |
| | IS FOR STAIR PRESSURIZATION NOT AIR |
| | CONDITIONING. |
| | |
| | THE A/C SHEET IS NOT SEALED BY THE |
| | ARCHITECT. |
| | |
| | SHEET A3 CONTAINS A NOTE REFERENCING |
| | ACCESSIBILITY.THE 11.1.6 (I) (F) |
| | SECTION CITED IS NOT FOUND IN THE FBC. |
| | PLEASE SEE FBC 11-4.1.3 (5) AND FBC |
| | 11-4.1.6 (1), VERTICAL ACCESIBILITY IS |
| | REQUIRED. |
| | |
| | THE TRACO WINDOW NOA HAS ILLEGIBLE |
| | DRAWINGS. |
| | |
| | THE PLANS DO NOT SHOW THE PRESSURES FOR |
| | THE WINDOW DESIGN.SEE FBC 1606.1.7 #5. |
| | |
| | SEE PREVIOUS NOTES REGARDING IMPACT |
| | FEES. |