Plan Review Notes
Plan Review Notes For Permit 02110220
Permit Number 02110220
Review Stop M
Sequence Number 2
Notes
Date Text
2003-10-23 00:00:00PROVISO:
 DUCT SMOKE DETECTORS REQUIRED FOR UNITS
 THAT HAVE A DESIGN CAPACITY GREATER THAN
 2,000 CFM. DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT AS PER
 2001 FBC(M) 606.2.1. FAN SHUTDOWN BY
 DUCT SMOKE DETECTORS SHALL HAVE
 NOTIFICATION TO ALARM/STROBE AS PER
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.