| Plan Review Notes For Permit 02110220 |
| Permit Number |
02110220 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-23 00:00:00 | PROVISO: | | | DUCT SMOKE DETECTORS REQUIRED FOR UNITS | | | THAT HAVE A DESIGN CAPACITY GREATER THAN | | | 2,000 CFM. DUCT SMOKE DETECTORS SHALL BE | | | INSTALLED IN THE SUPPLY AIR DUCT AS PER | | | 2001 FBC(M) 606.2.1. FAN SHUTDOWN BY | | | DUCT SMOKE DETECTORS SHALL HAVE | | | NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|