Plan Review Notes
Plan Review Notes For Permit 02110220
Permit Number 02110220
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-14 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/ EXT LTS.
  
 2)NOTE: PLEASE SEE THAT WE ARE NOW
 UNDER THE 2002 NEC. 7/1/03
  
 3)NOTE: PLEASE SEE THAT LOAD ON SERVICE
 EXCEEDS RATING OF EXISTING 200A SERVICE.
 PLEASE INCREASE SERVICE SIZE AND
 CONDUCTOR SIZES. 310.16/240.6 ETC.
  
 4)NOTE: PLEASE ADJUST GROUNDING ELEC-
 -TRODE CONDUCTOR PER 250.66
  
 5)NOTE: PLEASE SEE THAT MAX OCP FOR
 3500W OF WATER HEATER IS 150% OF LOAD.
 MIN OCP IS 125%. PLEASE ADJUST THE 2P30A
 SHOWN.
  
 6)NOTE: PLEASE SEE PLANS, PLANS SHOW
 TWO PANELS? RISER SHOWS ONLY ONE.?
 PLEASE CLARIFY?
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEWING AND STAMPING.
 ONE SET OF OLD SHEETS MAYBE SUBMITTED
 FOR VERIFICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]