| 2003-10-14 00:00:00 | **************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. 215.5 |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/ EXT LTS. |
| | |
| | 2)NOTE: PLEASE SEE THAT WE ARE NOW |
| | UNDER THE 2002 NEC. 7/1/03 |
| | |
| | 3)NOTE: PLEASE SEE THAT LOAD ON SERVICE |
| | EXCEEDS RATING OF EXISTING 200A SERVICE. |
| | PLEASE INCREASE SERVICE SIZE AND |
| | CONDUCTOR SIZES. 310.16/240.6 ETC. |
| | |
| | 4)NOTE: PLEASE ADJUST GROUNDING ELEC- |
| | -TRODE CONDUCTOR PER 250.66 |
| | |
| | 5)NOTE: PLEASE SEE THAT MAX OCP FOR |
| | 3500W OF WATER HEATER IS 150% OF LOAD. |
| | MIN OCP IS 125%. PLEASE ADJUST THE 2P30A |
| | SHOWN. |
| | |
| | 6)NOTE: PLEASE SEE PLANS, PLANS SHOW |
| | TWO PANELS? RISER SHOWS ONLY ONE.? |
| | PLEASE CLARIFY? |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS THAT MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEWING AND STAMPING. |
| | ONE SET OF OLD SHEETS MAYBE SUBMITTED |
| | FOR VERIFICATION. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |