| Plan Review Notes For Permit 02110132 |
| Permit Number |
02110132 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-14 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE DO NOT CORRELATE | | | WITH MASTER PLANS.02041269 | | | | | | 2)NOTE: MISSING ARC FAULT PROTECTION | | | FOR BEDROOM CRICUITS PER 210-12 | | | | | | 3)NOTE: MISSING REQ`D BATH CIRCUIT(S) | | | PER 210-11-C-3 | | | | | | 4)NOTE: PLEASE SEE DRYER SHOWN AT 1-POLE | | | 20A BRKR. | | | | | | PLEASE SEE PLANS, OTHER CHANGES WERE | | | MADE ALSO. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EDXT 8372 |
|