| Plan Review Notes For Permit 02110128 |
| Permit Number |
02110128 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-23 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 11/22/02: | | | | | | 3) SHEET A-05.REMOVAL OF COLUMN | | | BETWEEN THE LIVING ROOM AND MASTER | | | BEDROOM WIC.THIS COLUMN WAS SUPPORTING | | | GIRDER TRUSS SG2 AND WAS SUBJECT TO AN | | | UPLIFT OF 4911 LBS (SEE 'FLORIDA QUALITY | | | TRUSS' DESIGN).THE PROPOSED REVISION | | | OMITS THE COLUMN AND RELOCATES THE | | | GIRDER TRUSS WITHOUT HIGHLIGTHING THE | | | NEW SUPPORT POINTS AND STATING THE | | | RESPECTIVE UPLIFTS.SHEET A-05 SHALL BE | | | REVISED TO CLEARLY SHOW THE LOCATION AND | | | MAGNITUDE OF THE UPLIFT FORCES. |
|