| Permit Number |
02110125 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-14 00:00:00 | ************** UNSAT ************ | | | | | | 1)NOTE : PLEASE NOTE PLANS DO NOT | | | CORRELATE TO THE MASTER PLAN SUBMITTED | | | UNDER 02041269. | | | PLANS MUST BE THE SAME. | | | | | | 2)NOTE: PLEASE SEE THE REQ`D DEDICATED | | | BATH(S) CIRCUITS HAVE BEEN REMOVED? | | | 210-52D,210-11-C3 | | | | | | 3)NOTE: PLEASE SEE THE REQ`D ARC FAULT | | | CIRCUITS HAVE ALSO BEEN REMOVED ?? | | | 210-12 | | | | | | 4)NOTE: PLEASE SEE ORIG PLANS AND SEE | | | OTHER ITMES THAT HAVE BEEN CHANGED/ | | | REMOVED ETC. | | | | | | 5)NOTE: PLEASE NOTE DRYER SHOWN AS A | | | 1-POLE 20A ? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|