2003-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A) PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED.
 1) SHT D-1 ALL PLUMMBING, SANITARY/WATER
 LINES CAPPED SHALL BE INSPECTED PRIOR TO
 COVERING.
 2) SHT M/E-1 PLUMBING NOTES #1, CODE IN
 EFFECT IS FBC-2001 PLUMBING NOT STANDARD
 PLEASE CHANGE REFERENCE.
 3) SHT M/E-1 PLUMBING RISER SHALL RE-
 FLECT THE FLOOR PLAN. THE LAUNDRY ROOM
 IS TO THE LEFT OF THE KITCHEN, NOT BE-
 TWEEN THE KITCHEN AND BATH RISERS. ALSO
 THE LAUNDRY TRAY IS NOT SHOWN ON THE
 RISER. A CLEANOUT IS REQUIRED ON RISER
 ABOVE THE WASH MACHINE MINIMUM OF 4'
 ABOVE FINISHED FLOOR.
 4) SHT M/E-1 PLUMBING RISER, ISLAND VENT
 DOES NOT MEET CODE. (SUGGEST AN AIR AD-
 MITTENCE VALVE)
 5) PER BLDG OFFICIAL, ONCE A PLAN COMES
 IN FOR REVIEW WITH A RISER DIAGRAM, A
 RISER DIAGRAM SHALL BE REQUIRED.
  