2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT D-1 ALL PLUMBING, SANITARY/WATER
 LINES CAPPED SHALL BE INSPECTED PRIOR TO
 COVERING.
 2) SHT M/E-1 PLUMBING NOTES #1, CODE TO
 READ FBC-2001 PLUMBING NOT STANDARD.
 3) SHT M/E-1 PLUMBING RISER SHALL RE-
 FLECT THE FLOOR PLAN. THE LAUNDRY ROOM
 IS TO THE LEFT OF THE KITCHEN, NOT BE-
 TWEEN THE KITCHEN AND BATH RISERS. ALSO
 LAUNDRY TRAY IS NOT SHOWN ON RISER.
 CLEAN OUT REQUIRED ON RISER ABOVE WASH
 MACHINE MINIMUM OF 4' AFF.
 4) SHT M/E-1 PLUMBING RISER, ISLAND VENT
 DOES NOT MEET CODE. (SUGGEST AN AIR AD-
 MITTENCE VENT)
  
 REVIEW BY KEN STEVENS