| Plan Review Notes For Permit 02110117 |
| Permit Number |
02110117 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT D-1 ALL PLUMBING, SANITARY/WATER | | | LINES CAPPED SHALL BE INSPECTED PRIOR TO | | | COVERING. | | | 2) SHT M/E-1 PLUMBING NOTES #1, CODE TO | | | READ FBC-2001 PLUMBING NOT STANDARD. | | | 3) SHT M/E-1 PLUMBING RISER SHALL RE- | | | FLECT THE FLOOR PLAN. THE LAUNDRY ROOM | | | IS TO THE LEFT OF THE KITCHEN, NOT BE- | | | TWEEN THE KITCHEN AND BATH RISERS. ALSO | | | LAUNDRY TRAY IS NOT SHOWN ON RISER. | | | CLEAN OUT REQUIRED ON RISER ABOVE WASH | | | MACHINE MINIMUM OF 4' AFF. | | | 4) SHT M/E-1 PLUMBING RISER, ISLAND VENT | | | DOES NOT MEET CODE. (SUGGEST AN AIR AD- | | | MITTENCE VENT) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|