Plan Review Notes
Plan Review Notes For Permit 02110117
Permit Number 02110117
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE #6 EQUIPMENT GROUND RAN BETWEEN
 THE METER AND THE PANEL IS CREATING A
 PARALLEL GROUND PATH WITH THE GROUNDED
 CONDUCTOR (NEUTRAL) AND CANNOT BE
 INSTALLED PER 250-24(A)(1).
  
 3} PLEASE NOTE THE GEC SYSTEM MUST
 COMPLY WITH 250-50,SHOW SAME ON PLANS.
  
 4} THE WATER HEATER ON CIRCUITS 18 & 20
 DOES NOT HAVE THE CORRECT OVERCURRENT
 FOR THE LOAD SERVED.
  
 5} PLEASE NOTE THAT THE LAUNDRY CIRCUIT
 MUST COMPLY WITH 220-16(B).SHOW SAME IN
 CALCS & SCHEDULES.
  
 6} PLEASE NOTE THE DRYER MUST COMPLY
 WITH 220-18,IT IS SHOWN AS 1200VA ON
 THE SCHEDULE.
  
 7} THE WATER HEATER LISTED ON CIRCUITS
 9 & 11 @ 5000VA HAS AN OCP OF 40
 AMPS,PLEASE CLARIFY.
  
 8} AHU #1,CIRCUITS 15 & 17 LISTS THE OCP
 AND THE WIRE SIZE INCORRECTLY.
  
 9} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.LIST SAME ON
 SCHEDULE.
  
 10} NOTE THAT SERVICE RECEPTACLES ARE
 REQUIRED IN ATTICS PER 210-63.
  
 11} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 12} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 13} PLEASE NOTE THAT FAN SUPPORTS MUST
 COMPLY WITH 422-18.
  
 14} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392