| Date |
Text |
| 2002-11-04 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION, MAKE ANY NECESSARY CHANGES |
| | ON PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} THE #6 EQUIPMENT GROUND RAN BETWEEN |
| | THE METER AND THE PANEL IS CREATING A |
| | PARALLEL GROUND PATH WITH THE GROUNDED |
| | CONDUCTOR (NEUTRAL) AND CANNOT BE |
| | INSTALLED PER 250-24(A)(1). |
| | |
| | 3} PLEASE NOTE THE GEC SYSTEM MUST |
| | COMPLY WITH 250-50,SHOW SAME ON PLANS. |
| | |
| | 4} THE WATER HEATER ON CIRCUITS 18 & 20 |
| | DOES NOT HAVE THE CORRECT OVERCURRENT |
| | FOR THE LOAD SERVED. |
| | |
| | 5} PLEASE NOTE THAT THE LAUNDRY CIRCUIT |
| | MUST COMPLY WITH 220-16(B).SHOW SAME IN |
| | CALCS & SCHEDULES. |
| | |
| | 6} PLEASE NOTE THE DRYER MUST COMPLY |
| | WITH 220-18,IT IS SHOWN AS 1200VA ON |
| | THE SCHEDULE. |
| | |
| | 7} THE WATER HEATER LISTED ON CIRCUITS |
| | 9 & 11 @ 5000VA HAS AN OCP OF 40 |
| | AMPS,PLEASE CLARIFY. |
| | |
| | 8} AHU #1,CIRCUITS 15 & 17 LISTS THE OCP |
| | AND THE WIRE SIZE INCORRECTLY. |
| | |
| | 9} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG.LIST SAME ON |
| | SCHEDULE. |
| | |
| | 10} NOTE THAT SERVICE RECEPTACLES ARE |
| | REQUIRED IN ATTICS PER 210-63. |
| | |
| | 11} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 12} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 13} PLEASE NOTE THAT FAN SUPPORTS MUST |
| | COMPLY WITH 422-18. |
| | |
| | 14} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ'D PER 210-52(E). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT.8392 |