Plan Review Notes
Plan Review Notes For Permit 02110117
Permit Number 02110117
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-06 00:00:00SHEET A4 SHOWS DETAIL 1/A6 TAKEN IN
 FOURSEPARATE PLACES OF DIFFERING
 CONDITIONS AND IS NOT DETAILED ON THE
 PLAN.PLEASE CLARIFY AS NECESSARY.THE
 INFORMATION FOR THE TRANSITION OF THE
 NEW CONCRETE BEAM TO THE OLD, THE
 GIRDER CONNECTIONS TO THE CMU, AND
 OTHER DETAILS ARE IMPORTANT.
  
 SECTION 1/A8 SHOWS A CONTINUOUS 2"
 SCREENED SOFFIT VENT.PROVIDE AN
 ANALYSIS, INCLUDING THE FREE AREA OF
 THE VENT THAT DEMONSTRATES COMPLIANCE
 WITH FBC 2309.7, ALSO SHOW THE ATTIC
 ACCESS IN ACCORDANCE WITH FBC 2309.6.
  
 SECTION 2/A8 AND ELSEWHERE, SHOW THE
 SPEICIFICATION FOR THE GUARD RAIL AND
 HAND RAILS.SEE FBC 1007.5 AND FBC
 1015.
  
 PLEASE MARK THE COMPONENTS TO BE USED
 FOR THE HURRICANE SHUTTERS IN SBCCI
 REPORT
 2211.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE WINDOWS, DOORS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, SEPARATE PERMITS
 AND FEES WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-253-5025 FOR
 MORE INFORMATION.
  
 A COPY OF A RECORDED NOTICE OF
 COMMENCEMENT MUST BE PROVIDED TO THE
 CITY PRIOR TO THE PERMIT BEING ISSUED.