2002-12-02 00:00:00DENIED:
  
 PROVIDE LOCATION FOR THE TERMINATION OF
 CONDESATE (DRYWELL, STORM?).INDICATE
 WHERE THE TERMINATION OF THE EMEREGENCY
 DRAIN WILL BE LOCATED.AS PER 2001
 FBC(M) 307.2.3, AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT THE PRIMARY
 DRAIN IS RESTRICTED.
  
 PROVISO:
 EQUIPMENT RACK FOR CONDENSER SHALL
 COMPLY WITH 2001 FBC 1511.7, IF THIS IS
 A NEW INSTALLATION & NOT EXISTING.
 SEE PLAN SHEET MP-2.
  