Plan Review Notes
Plan Review Notes For Permit 02110098
Permit Number 02110098
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-22 00:00:001) CURTAIN BY TENANT NEAR STOCKROOM IS
 NOT ALLOWED. PLEASE SEE NFPA 101,
 THE LIFE SAFETY CODE, 2000 EDITION,
 SECTION 7.1.10.2.1.
  
 2) WHEN PAINTING CEILING, EXTREME CARE
 SHALL BE TAKEN TO PREVENT THE
 APPLICATION OF PAINT TO EXISTING
 SPRINKLER HEADS. IF FIRE SPRINKLER
 HEADS ARE PAINTED, THEY ARE TO BE
 REPLACED AND NOT CLEANED.
  
 3) A FIRE SPRINKLER HEAD IS REQUIRED
 DIRECTLY OUTSIDE OF THE ENTRY DOOR.
 (VESTIBULE)
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910