| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | DENIED: | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC(M) 403.3 OR ASHRAE | | | 62-89. | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL FOR | | | THE CONDENSER UNIT STAND.SHOW | | | COMPLIANCE WITH 2001 FBC 1511.7 - | | | MINIMUM CLEARANCE REQUIRED BETWEEN | | | THE ROOF SURFACE & THE BOTTOM OF THE | | | SUPPORT RAIL.SEE ATTACHED. | | | | | | 3.BATHROOMS SHALL HAVE MECHANICAL | | | EXHAUST AS PER 2001 FBC(M) 503.13 & | | | 402.3.1. | | | | | | 4.RETURN AIR REQUIRED FROM ROOM | | | THAT CAN BE ISOLATEDFROM THE | | | RETURN AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|