| 2002-12-03 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | TO THE PLAN,AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 4} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | MUST HAVE A BATTERY BACK UP PER 905.2.5 |
| | FBC. |
| | |
| | 5} THE ISLAND IN THE KITCHEN MUST COMPLY |
| | WITH 210-52(C)(2). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392 |