2002-12-13 00:00:00BUILDING DENIED
  
 1) NOTE #11 OF THE PLAN NOTES ON SHEET
 C1 STATES THAT HURRICANE PANELS ARE
 REQUIRED IN HVHZ. THEY ARE REQUIRED IN
 THE CITY OF WPB, WHICH IS NOT IN A HVHZ,
 BUT IS IN THE WIND-BORNE DEBRIS REGION.
 PLEASE REVISE. FBC CHAPTER 16.
  
 2) THE FBC SECTION 1707.4.4.2 STATES
 THAT WHERE WOOD BUCKS ARE LESS THAN
 1-1/2 INCHES THICK THE WINDOW AND DOOR
 ASSEMBLIES ARE REQUIRED TO BE ANCHORED
 THROUGH THE JAMB INTO THE STRUCTURAL
 SUBSTRATE. PLEASE REVISE THE SLIDING
 GLASS DOOR BUCK DETAIL ON A4.
  
 3) FBC SECTION 1707.4.4.2 REQUIRES BUCKS
 1-1/2 INCHES THICK OR GREATER TO EXTEND
 TO THE INTERIOR FACE OF THE JAMB. PLEASE
 REVISE DOOR HEAD/JAMB DETAIL ON A8.
  
 4) SPECIFY THE SIZE AND SPECIES OF WOOD
 FOR THE WOOD POST SHOWN ON A5.
  
 5) THE ENERGY CALC. FORM IS REQUIRED TO
 BE SIGNED BY THE OWNER/AGENT.
  
 6) PROVIDE THE LISTING INFORMATION AND
 MANUFACTURER'S SPECIFICATIONS FOR A ONE
 HOUR RATED FIRE ASSEMBLY FOR THE GLASS
 BLOCK.
  
 7)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SH WINDOWS (EXPIRED)
 - OUTSWING DOUBLE DOORS (EXPIRED)
  
 8) THE PRODUCT APPROVALS FOR THE
 MULLIONS DO NOT HAVE DESIGN WINDLOADS
 FOR A MULLION LENGTH OF 144" AND AN
 OPENING WIDTH OF 120", WHICH IS REQUIRED
 AT THE SLIDING GLASS DOOR AND FIXED
 GLASS WINDOW ASSEMBLY.
  
 9) THE SITE SPECIFIC PRODUCT APPROVAL
 FORM FOR THE OVERHEAD GARAGE DOORS IS
 NOT ACCEPTABLE. IT MUST REFERENCE THE
 THE 2001 FBC, BE SIGNED, SEALED AND
 DATED BY THE PRODUCT ENGINEER AND THE
 DESIGNER OF RECORD, AND THE LOCATION OF
 THE JOB IS REQUIRED. SUBMIT THE SBCCI
 PRODUCT EVALUATION REPORT #9606C THAT
 ACCOMPANIES THE DRAWING.
  
 10)THE STORM PANEL INSTALLATION SCHEDULE
 IS NOT CORRECT FOR THE VERTICAL
 INSTALLATION ON THE MULLED WINDOWS. THE
 SHUTTERS MUST SPAN THE ENTIRE OPENING
 PLUS THE REQUIRED EDGE DISTANCE. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202