| Plan Review Notes For Permit 02102235 |
| Permit Number |
02102235 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING. | | | | | | A) COMMENT FROM 1ST AND 2ND REVIEW NOT | | | ADDRESSED. | | | 1) SHT A-16 CARRISA MODEL, BEGONIA MODEL | | | & DATURA MODEL, SANT DRAIN REQUIRED TO | | | BE MINIMUM OF 3" UP TO WHERE THE TUB IS | | | TAKEN OFF BRANCH DRAIN. TABLE 909.3 & | | | SECTION 909.1 WET VENT. SINCE THIS IS | | | A MASTER MODEL, IT SHALL BE CORRECTED TO | | | MEET CODE REQUIREMENTS. | | | SEE FLORIDA STATUTE 553.80(2)(B) ATTACH- | | | ED FOR IMFORMATION CONCERNING 4 TIMES | | | THE FEE AFTER 3RD REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|