| Plan Review Notes For Permit 02102235 |
| Permit Number |
02102235 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-03 00:00:00 | DENIED:2ND PLAN CHECK UNITS A,B,C & D | | | | | | COMMENTS FROM PLAN CHECK DATED 11-30-02 | | | NOT ADDRESSED. | | | | | | 1.INDICATE OUTSIDE AIR REQUIREMENT BY | | | NATURAL 2001 FBC(M) 402.2 OR MECHANCIAL | | | TABLE 403.3.PROVIDE CALCULATIONS. | | | | | | 2.MISSING DUCT SIZE FROM MODEL C THE | | | MASTER BEDROOM SUPPLY DUCT.8"? | | | | | | 3.SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|