| Plan Review Notes For Permit 02102235 |
| Permit Number |
02102235 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-19 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE CORRECT THE FOLLOWING AND | | | RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | ELECTRICAL INSPECTIONS. | | | | | | 1} NOTE #18 ON SHEET C1 MAKES A | | | REFERENCE TO "ALL DWELLING ROOM | | | RECEPTACLES" BEING ON ARC FAULT | | | BREAKERS,WHICH CONTRADICTS THE NOTE ON | | | A-16.PLEASE CORRECT TO SHOW THE INTENT | | | OF THE ARCHITECT. | | | | | | 2} THERE ARE NO MAIN DISCONNECTS SHOWN | | | ON THE RISER DIAGRAM AND PANELS ARE | | | SWOWN AS MLO.PLEASE | | | CLARIFY.(DISCONNECTS ARE SHOWN ON SHEET | | | A-10 OF THE DRAWING). | | | | | | 3} THE LIVING ROOM IN UNIT "A",AND THE | | | GREAT RM IN UNIT "C" HAVE RECEPTACLE | | | SPACING NOT IN COMPLIANCE WITH 210-52, | | | PLEASE CORRECT. | | | | | | 4} THE ELEVATOR OCP ON PANELS "C&D" DO | | | NOT MATCH THE THE ELEVATOR SPEC'S FOR | | | 30AMPS.PLEASE CLARIFY AND RECALCULATE | | | THE PANEL LOADS IF NECESSARY. | | | | | | 5} PLEASE NOTE THAT MOST OF THE | | | EQUIPMENT DISCONNECTS ARE NOT SHOWN TO | | | COMPLY WITH 110-26.PLEASE CHANGE THE | | | DRAWINGS TO SHOW COMPLIANCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|