2003-03-19 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE FOLLOWING AND
 RESUBMIT FOR REVIEW PRIOR TO ROUGH
 ELECTRICAL INSPECTIONS.
  
 1} NOTE #18 ON SHEET C1 MAKES A
 REFERENCE TO "ALL DWELLING ROOM
 RECEPTACLES" BEING ON ARC FAULT
 BREAKERS,WHICH CONTRADICTS THE NOTE ON
 A-16.PLEASE CORRECT TO SHOW THE INTENT
 OF THE ARCHITECT.
  
 2} THERE ARE NO MAIN DISCONNECTS SHOWN
 ON THE RISER DIAGRAM AND PANELS ARE
 SWOWN AS MLO.PLEASE
 CLARIFY.(DISCONNECTS ARE SHOWN ON SHEET
 A-10 OF THE DRAWING).
  
 3} THE LIVING ROOM IN UNIT "A",AND THE
 GREAT RM IN UNIT "C" HAVE RECEPTACLE
 SPACING NOT IN COMPLIANCE WITH 210-52,
 PLEASE CORRECT.
  
 4} THE ELEVATOR OCP ON PANELS "C&D" DO
 NOT MATCH THE THE ELEVATOR SPEC'S FOR
 30AMPS.PLEASE CLARIFY AND RECALCULATE
 THE PANEL LOADS IF NECESSARY.
  
 5} PLEASE NOTE THAT MOST OF THE
 EQUIPMENT DISCONNECTS ARE NOT SHOWN TO
 COMPLY WITH 110-26.PLEASE CHANGE THE
 DRAWINGS TO SHOW COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW